Technical Data
Acoustics
N/A
|
Ceiling
OTH
CEILING - OTHERWater resistant and easy clean ceiling |
Communications
CO
COMMUNICATIONS/TELEPHONE POINTSData points required. Refer to DG / COMMUNICATIONS AUDIO VISUAL REQUIREMENTSAlarm call button system required, Refer to DG / COMMUNICATIONS |
Cooling
N/A
|
Doors
DT
DOOR TYPEEnsure visual privacy (consider reflections in mirrors). Minimum 1m wide clear opening For Types 2-4 - Solid Core Door without closer preferred. Curtain may be used internally for visual privacy Refer to DG / DOORS |
Drainage
SD
SANITARY DRAINAGE FIXTURES3 Drainage outlets Refer to DG / DRAINAGE |
Fire Protection
FD
FIRE DETECTION/ALARMSFire detection/alarms to comply with NCC. Refer to DG / THERMAL/SMOKE DETECTORS |
Floor
FF
FLOOR FINISHCT- Ceramic tiles. Refer to DG / FLOOR FLOOR WASTEFloor waste(s) are to be included with falls in floor. Refer to DG / DRAINAGE (& TRADE WASTE) FLOOR - OTHERWater Resistant Floor Coved skirting Grade floor to flow waste for drainage Tiling to have flush joints and not to have a bevelled edge. Avoid abrupt changes in level. Refer to DG / FLOOR |
|
Heating
OTH
HEATING - OTHERInclude local heating to shower area. Refer to DG / HOT WATER HEATERS |
Illumination
LUX
LUX LEVEL160 lux Refer to DG / LIGHTING LIGHTING CONTROL |
Keying
KY
KEYING GENERALKeyed Alike Toilets (T). Refer to SG / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration & Staff (AF). Refer to SG / DOOR HARDWARE / KEYING |
Light
N/A
|
Planning
m^2
AREAType 2 - 20m2 Type 3 - 20m2 Type 4 - 29m2 Refer to DG / AREA PLANNING - OTHERWhere multiple access WC's provided ensure equal numbers of each hand. Ensure visual privacy of toilet and change room area. Refer to DG / AREA PROPORTIONGenerally layout to suit fittings. At least one cubicle per group of toilets to be designed as an Ambulant Accessible WC to meet regulations. All designs should meet regulatory requirements. Refer to DG / AREA |
Power
N/A
|
Security
A
SECURITY LEVEL ACategory A - Low Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGE"TOILET" Refer to DG / DOOR SIGNS SIGNS GENERALBraille and Tactile signage as required by access regulations. Notice "Assistance required in Access Shower/Toilet when buzzer sounds", in nearest permanently occupied space. Refer to DG / SIGNS |
Ventilation
NV
NATURAL VENTILATIONProvide Natural Ventilation. Refer to DG / VENTILATION and DG / AIR MOVEMENT / NATURAL VENTILATION GENERAL EXHAUSTMechnical exhaust. Refer to DG / VENTILATION |
Wall
OTH
WALL - OTHERWater resistant, easy-clean walls. Masonry walls with tiled surfaces to door head height (for Type 2: tiled to 1.5m above floor). Refer to SG / LINING |
Water
HW
TEMPERED WATERTempered water required to 1 x basin, 1 x shr. Refer to DG / WATER COLD WATERCW Required to 1 x basin, 1 x WC, 1 x shr. Refer to DG / WATER |
Windows
OTH
WINDOWS - OTHERObscure glazing required to Ensure Visual privacy. Refer to DG / WINDOWS VISUAL PRIVACYVisual privacy is required from other spaces. |