Technical Data
Acoustics
N/A
|
Ceiling
OTH
CEILING - OTHERWater Resistant and easy clean ceiling. ACOUSTIC CEILING TYPEStandard ceiling Refer to DG / CEILING |
Communications
N/A
|
Cooling
N/A
|
Doors
DT
DOOR TYPEEnsure visual privacy (consider reflections in mirrors). External door to be grill gate. Refer to DG / DOORS |
Drainage
SD
SANITARY DRAINAGE FIXTURES3 Drainage outlets Refer to DG / DRAINAGE
|
Fire Protection
N/A
|
Floor
FF
FLOOR FINISHCT- Ceramic Tiles. Refer to DG / FLOOR FLOOR WASTEFloor waste(s) are to be included with falls in floor. Refer to DG / DRAINAGE (& TRADE WASTE) FLOOR - OTHERCoved skirting tiles at wall Well graded falls to floor waste. Refer to DG / FLOOR |
|
Heating
N/A
|
Illumination
LUX
LUX LEVEL160 lux. Refer to DG / LIGHTING LIGHTING CONTROLLighting control requirements as outlined in Design Guide. Refer to DG / LIGHTING |
Keying
KY
KEYING GENERALKeyed Alike Toilets (T). Refer to SG / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration & Staff (AF). Refer to SG / DOOR HARDWARE / KEYING |
Light
N/A
|
Planning
m^2
AREA2m2 Refer to DG / AREA PLANNING - OTHERAllow for one WC to be 1.2m wide per Sex per general student toilet group. At least 1 Ambulant cubicle per sex per group of toilets. Ensure visual privacy of cubicles. Refer to DG / AREA PROPORTIONArea varies depending upon number of students. Refer to DG / AREA |
Power
N/A
|
Security
A
SECURITY LEVEL ACategory A - Low Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGE"BOYS" or "GIRLS" Refer to DG / DOOR SIGNS SIGNS GENERALBraille and Tactile signage as required by access regulations. Notice "Assistance required in Access Shower/Toilet when buzzer sounds", in nearest permanently occupied space. Refer to DG / SIGNS |
Ventilation
NV
NATURAL VENTILATIONProvide Natural Ventilation. Refer to DG / VENTILATION and DG / AIR MOVEMENT / NATURAL VENTILATION GENERAL EXHAUSTMechnical exhaust. Refer to DG / VENTILATION |
Wall
OTH
WALL - OTHERWater resistant, easy-clean walls. 300mm high stainless steel splashback to wash trough. Refer to SG / LINING IMPACT RESISTANCEImpact resistant walls are recommended. Refer to DG / FABRIC |
Water
HW
TEMPERED WATERTempered water required to 1 x basin. Refer to DG / WATER COLD WATERCW Required to 1 x basin, 1 x WC (603.02) CW Required to 1 x basin, 1 x urinal (603.03). Refer to DG / WATER |
Windows
OTH
WINDOWS - OTHERFixed metal louvres preferred. Obscure glazing when required. Ensure visual privacy. Refer to DG / WINDOWS VISUAL PRIVACYVisual privacy is required from other spaces. |