Technical Data
Acoustics
NL
NOISE LEVELSNoise levels within this space should be considered. Refer to DG / ACOUSTICS / INTERNAL NOISE LEVELS ROOM TO ROOM NOISENoise to and from adjacent rooms should be considered. ROOM ACOUSTICSRoom acoustics, particularly reverberation time should be considered. |
Ceiling
ACC
ACOUSTIC CEILING TYPEStandard ceiling Refer to DG / CEILING |
Communications
CO
COMMUNICATIONS/TELEPHONE POINTS1 double data points required Refer to DG / COMMUNICATIONS AUDIO VISUAL REQUIREMENTSAudio visual facilites are required. WIRELESS ACCESS POINTS |
Doors
DT
DOOR TYPEAccordion door or operable door to adjacent Study Annexe (Type 3 minimum 2.4m wide) (Type 4 & 5 minimum 3.6m) Refer to DG / DOORS |
Drainage
SD
SANITARY DRAINAGE FIXTURES1 Drainage outlet Refer to DG / DRAINAGE |
|
Fire Protection
FD
FIRE DETECTION/ALARMSFire detection/alarms to comply with NCC. Refer to DG / FLOOR |
Floor
FF
FLOOR FINISHC - Carpet finish SV-Sheet Vinyl (not foam backed) to Kitchenette area. Refer to DG / FLOOR |
|
Heating
H
HEATINGProvide heating where regionally appropriate. Refer to DG / HEATING |
Illumination
LUX
LUX LEVEL240 lux. Refer to DG / LIGHTING LIGHTING CONTROLLighting control requirements as outlined in Design Guide.Refer to DG / LIGHTING |
Keying
KY
KEYING GENERALType 1 & 2 - Keyed to differ (KD) Type 3, 4 & 5 - Keyed Alike Staff Studies (SS). Refer to SG / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration & Staff (AF). Refer to SG / DOOR HARDWARE / KEYING |
Light
N/A
|
Power
CM
CABLE MANAGEMENTCable management to be considered. Refer to DG / POWER GENERAL POWER OUTLETS2 double socket outlets and 2 single sock outlets. Refer to DG / POWER |
|
Security
B
SECURITY LEVEL BCategory B - Moderately Low Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGE"STAFF" Refer to DG / DOOR SIGNS SAFETY SIGNSign with red writing and symbol “Warning – this fixture may deliver hot water which will scald.” -adjacent to the Boiling Water Unit & sink. Refer to DG / SIGNS |
Ventilation
NV
NATURAL VENTILATIONProvide Natural Ventilation. Refer to DG / VENTILATION and DG / AIR MOVEMENT / NATURAL VENTILATION |
Wall
PF
PINBOARD FINISHMaximise pinboard finish to 2100mm. Pinboard not required above splashback. Refer to SG / LINING WALL - OTHER450mm high water resistant splashback to sink and bench. Refer to SG / LINING |
Water
HW
HOT WATERHW required to 1 x sink. Refer to DG / WATER COLD WATERCW Required to 1 x sink, 1 x BWU (602.01). CW Required to 1 x sink, 1 x BWU, 1 x DW (602.02, 602.03 & 602.04). Refer to DG / WATER |
Windows
Y
WINDOWS - YWindows are required for this space. |