Technical Data
Acoustics
N/A
|
Ceiling
FR
RES
RESISTANCEImpact resistant ceiling required. Refer to DG / CEILING CEILING - OTHERImpact resistant ceiling. Fire rated ceiling may need to be included to provide separation from Multipurpose Space. Refer to 'Suggested Fixtures' list and SG / METALWORK / CEILING HOOK |
Communications
N/A
|
Cooling
N/A
|
Doors
DT
DOOR TYPE1.5 m minimum clear width opening. Doors to store to be fire rated (FRL -/60/30). Minimise threshold for movement of chair trolleys. Refer to DG / DOORS FIRE-RATED DOORSFire-rated doors are required. |
Drainage
N/A
|
Fire Protection
FD
FIRE DETECTION/ALARMSFire detection/alarms to comply with NCC. Refer to DG / THERMAL/SMOKE DETECTORS |
Floor
FF
FLOOR FINISHCC - Steel Trowel Concrete finish. Refer to DG / FLOOR FLOOR - OTHERMinimise threshold to enable movement of chairs. Refer to DG / FLOOR |
Gas
N/A
|
Heating
N/A
|
Illumination
|
Keying
KY
KEYING GENERALKeyed to differ (KD). Refer to SG455 / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Stores(ST). Refer to SG455 / DOOR HARDWARE / KEYING |
Light
N/A
|
Power
N/A
|
|
Security
C
SECURITY LEVEL CCategory C - Medium Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGE"P.E STORE". Refer to DG / DOOR SIGNS SAFETY SIGNIn a conspicuous internal position: notice stating "This Store is for PE/Sports Equipment or Chairs only." "Doors may only be open during Performances/Meetings if no flammable materials are present." Refer to DG / SIGNS |
Ventilation
N/A
|
Wall
OTH
WALL - OTHERIf part of building used as an Community Hall/ Entertainment Venue, store room to have Fire rated walls(FRL 60/60/60) to separate from Hall. Refer to SG / LINING IMPACT RESISTANCEImpact resistant walls are recommended. Refer to DG / FABRIC |
Water
N/A
|
Windows
N
WINDOWS - NWindows are not required for this space. WINDOWS - OTHERWhen windows are provided include obscure glazing and security grilles. Refer to DG / WINDOWS VISUAL PRIVACYVisual privacy is required from other spaces. |