Technical Data
Acoustics
N/A
|
Ceiling
ACC
ACOUSTIC CEILING TYPEStandard ceiling Refer to DG / CEILING |
Communications
CO
COMMUNICATIONS/TELEPHONE POINTS3 double data points required Refer to DG / COMMUNICATIONS AUDIO VISUAL REQUIREMENTSAudio visual facilities are required. Refer to DG / COMMUNICATIONS |
Cooling
|
Doors
DT
DOOR TYPEDoor minimum 900mm clear width for equipment Refer to DG / DOORS |
Drainage
N/A
|
Fire Protection
FD
FIRE DETECTION/ALARMSFire detection/alarms to comply with NCC. Refer to DG / THERMAL/SMOKE DETECTORS |
Floor
FF
FLOOR FINISHASV - Anti Static Vinyl. Refer to DG / FLOOR |
Gas
N/A
|
Heating
N/A
|
Illumination
LUX
LUX LEVEL240 lux. Refer to DG / LIGHTING LIGHTING CONTROLLighting control requirements as outlined in Design Guide. Refer to DG / LIGHTING |
Keying
KY
KEYING GENERALKeyed to differ (KD) Refer to SG / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration and Staff facilities (AF) Refer to SG / DOOR HARDWARE / KEYING |
Light
N/A
|
Power
CM
CABLE MANAGEMENTCable management to be considered. Refer to DG / POWER GENERAL POWER OUTLETS5 double socket outlets and 3 single sock outlets. Refer to DG / POWER |
|
Security
D
SECURITY LEVEL DCategory D - Moderately High Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGE"COMUNICATIONS ROOM" Refer to DG / DOOR SIGNS WARNING SIGNHazard danger sign "ELECTRICAL EQUIPMENT - AUTHORISED PERSONNEL ONLY", on the exterior of door. Refer to DG / SIGNS |
Ventilation
N/A
|
Wall
N/A
|
Water
N/A
|
Windows
N
WINDOWS - NWindows are not required for this space. WINDOWS - OTHERWindows not to be provided. Refer to DG / WINDOWS VISUAL PRIVACYVisual privacy is required from other spaces. |