Acoustics
R2R
ROOM TO ROOM NOISENoise to and from adjacent rooms should be considered. |
Ceiling
ACC
ACOUSTIC CEILING TYPEStandard ceiling. Refer to DG / CEILING |
Communications
CO
COMMUNICATIONS/TELEPHONE POINTS4 Dual Data Point required. Refer to DG / COMMUNICATIONS WIRELESS ACCESS POINTSThe rooms to be wireless enabled Refer to DG / COMMUNICATIONS |
Cooling
MC
MECHANICAL COOLINGMechanical Cooling required in all regions (24/7/365) - Airconditioning is mandatory in any new or refurbished main commiunications room(MCR) |
Doors
DT
DOOR TYPENo Window Door OtherMinimum opening height 2100mm Minimum opening width 1000mm |
Drainage
N/A
|
Fire Protection
PFE
PORTABLE FIRE EXTINGUISHER/BLANKETPortable fire extinguisher required.Comply with NCC. FIRE HOSE REELFire hose reels as required to comply with NCC. |
Floor
FF
FLOOR FINISHAnti-static vinyl/Linoleum finish |
Gas
N/A
|
Heating
N/A
|
Illumination
OTH
OTHER2 lights minimum, illuminating front and rear of cabinets LUX LEVEL500 Lux LIGHTINING CONTROL |
Keying
KY
KEYING GENERALKeyed Alike ‐ Building Communications Room (SA) Refer to SG455 / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration & Staff Facilities (AF). |
Light
N/A
|
Power
CM
CABLE MANAGEMENTCable management to be considered. GENERAL POWER OUTLETS4 Double Socket Outlets. POWER - OTHER8 captive 15A pendant sockets Each on dedicated Circuit Additional General Power Outlets may be required for Security Equipment. Refer to Security Specifications. Other power considerations may apply
|
|
Security
D
SECURITY LEVELCategory D ‐ Moderately High Security Level applies |
Signs
DSF
DOOR SIGNAGEDoor signage required. Suggested text "Communications Room". SIGNS - OTHERHazard danger sign "ELECTRICAL EQUIPMENT - AUTHORISED PERSONNEL ONLY" on the exterior of door. |
Ventilation
EXH
GENERAL EXHAUSTProvide general exhaust if communications rack is in room. |
Wall
N/A
|
Water
N/A
|
Windows
N
WINDOWS - NWindows are not required for this space. OBSERVATION WINDOWS |
Room Relationships
This space is found in the Services . This room shouuld be centrally located and secured.This room should be physically located to reduce cable pathway lengths and near building risers.
Maximum fixed cable pathway length is 90M, Use 70M radius as approximate working guide for cable coverage.To be located in a secure location with no external or student access.