Technical Data
Acoustics
N/A
|
Ceiling
RES
RESISTANCEWater Resistant Ceiling. Refer to DG / CEILING |
Communications
N/A
|
Cooling
N/A
|
Doors
DT
DOOR TYPEEnsure visual privacy (consider reflections in mirrors). External door to be grill gate. Refer to DG / DOORS |
Drainage
SD
SANITARY DRAINAGE FIXTURESDrainage outlets required. Refer to DG / DRAINAGE |
Fire Protection
N/A
|
Floor
FF
FLOOR FINISHCT - Ceramic Tiles. Refer to DG / FLOOR FLOOR WASTEFloor waste(s) are to be included with falls in floor. Refer to DG / DRAINAGE (& TRADE WASTE) FLOOR - OTHERCoved skirting tiles at wall Well graded falls to floor waste. Refer to DG / FLOOR |
|
Heating
N/A
|
Illumination
|
Keying
KY
KEYING GENERALKeyed Alike Toilets (T). Refer to SG / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration & Staff (AF). Refer to SG / DOOR HARDWARE / KEYING |
Light
N/A
|
Power
N/A
|
|
Security
A
SECURITY LEVEL ACategory A - Low Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGE"BOYS "or "GIRLS" Refer to DG / DOOR SIGNS SIGNS GENERALBraille and Tactile signage as required by access regulations Notice "Assistance required in Access Shower/Toilet when buzzer sounds", in nearest permanently occupied space. Refer to DG / SIGNS |
Ventilation
NV
NATURAL VENTILATIONProvide Natural Ventilation. Refer to DG / VENTILATION and DG / AIR MOVEMENT / NATURAL VENTILATION |
Wall
OTH
WALL - OTHERWater resistant, easy-clean walls. 300mm high Stainless steel splashback to wash trough. Refer to SG / LINING IMPACT RESISTANCEImpact resistant walls are recommended. Refer to DG / FABRIC |
Water
CW
COLD WATERRequired to WC's, wash trough (& urinals where applicable). Refer to DG / WATER |
Windows
OTH
WINDOW - OTHERFixed metal louvres preferred. Obscure glazing when required. Ensure Visual privacy. Refer to DG / WINDOWS VISUAL PRIVACYVisual privacy is required from other spaces. |