Technical Data
Acoustics
N/A
|
Ceiling
N/A
|
Communications
N/A
|
Cooling
N/A
|
Doors
DT
DOOR TYPEPermanent high and low level openings for air change. Cylinders require protection from tampering or damage. Doors and frames non-combustible and visually-screened for security. Refer to DG / DOORS |
Drainage
N/A
|
Fire Protection
N/A
|
Floor
FF
FLOOR FINISHCC - Steel Trowel Concrete. Refer to DG / FLOOR |
Gas
N/A
|
Heating
N/A
|
Illumination
LUX
LUX LEVEL160 lux. Refer to DG / LIGHTING LIGHTING CONTROLLighting control requirements as outlined in Design Guide. Refer to DG / LIGHTING |
Keying
KY
KEYING GENERALKeyed to Differ (KD). Refer to SG / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Stores (ST). Refer to SG / DOOR HARDWARE / KEYING |
Light
N/A
|
Planning
m^2
AREA1m2 Refer to DG / AREA PLANNING - OTHERMust comply with Dangerous Goods Regulations and Standards. Allow for 8 x 9kg LPG cylinders, 310mm dia x 510mm high. Provide clearance around tank and valves. Must be separated from any building opening by more than 1m. cylinder valve to be 150mm min below any operable window. Must be 3m min from flammable liquids storage over 250L. If acetylene stored as well then tanks must be 3m from any oxidant or separated by a vapour barrier 1.5m high min. Refer to DG / AREA PROPORTIONTo suit LPG tank storage. Refer to DG / AREA |
Power
N/A
|
Security
B
SECURITY LEVEL BCategory B - Moderately Low Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGE" LPG STORE". Refer to DG / DOOR SIGNS SIGNS GENERALSAFETY NOTICE Mandatory sign "LPG STORAGE MAX 300 KG", internally. Hazardous Materials sign "FLAMMABLE GAS" - class 2. Prohibition sign "No Smoking" symbol, outside the Store and adjacent to entry. Refer to DG / SIGNS |
Ventilation
NV
NATURAL VENTILATIONProvide Natural Ventilation. Refer to DG / VENTILATION and DG / AIR MOVEMENT / NATURAL VENTILATION |
Wall
FR
FIRE RATED WALLWALL - OTHERNon-combustible wall lining. Refer to SG / LINING IMPACT RESISTANCEImpact resistant walls are recommended. Refer to DG / FABRIC |
Water
N/A
|
Windows
N
WINDOWS - NWindows are not required for this space. VISUAL PRIVACYVisual privacy is required from other spaces. |