Technical Data
Acoustics
N/A
|
Ceiling
RES
RESISTANCEWater Resistant Ceiling. Refer to DG / CEILING |
Communications
N/A
|
Cooling
N/A
|
Doors
N/A
|
Drainage
SD
SANITARY DRAINAGE FIXTURES6 drainage outlets. Refer to DG / DRAINAGE |
Fire Protection
FHR
FIRE HOSE REELFire Hose Reels as required to comply with NCC. Refer to DG / BUILDING REGULATIONS & BUILDING CODE OF AUSTRALIA / SERVICES AND EQUIPMENT |
Floor
FF
FLOOR FINISHCT - Ceramic Tiles graded to falls. Refer to DG / FLOOR FLOOR WASTEFloor waste(s) are to be included with falls in floor. Refer to DG / DRAINAGE (& TRADE WASTE) |
|
Heating
N/A
|
Illumination
LUX
LUX LEVEL160 lux. Refer to DG / LIGHTING LIGHTING CONTROLLighting control requirements as outlined in Design Guide. Refer to DG / LIGHTING
|
Keying
KY
KEYING GENERALKeyed Alike - Toilets (T). Refer to SG / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration and Staff Facilities (AF). Refer to SG / DOOR HARDWARE / KEYING |
Light
N/A
|
Power
N/A
|
|
Security
B
SECURITY LEVEL BCategory B - Moderately Low Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGE"BOYS or GIRLS" Refer to DG / DOOR SIGNS |
Ventilation
N/A
|
Wall
OTH
WALL - OTHERWalls to be impact resistant and easy clean, with Ceramic tiles to 1.8m above floor in shower areas. Refer to SG / LINING IMPACT RESISTANCEImpact resistant walls are recommended. Refer to DG / FABRIC |
Water
HW
TEMPERED WATERRequired to 4 x showers. Refer to DG / WATER COLD WATERRequired to 4 x showers, 1 x wash trough, 1 x WC, 1 x hose cock. Refer to DG / WATER |
Windows
OTH
WINDOWS - OTHERIf windows are included obscure glazing and consider privacy when windows open for ventilations and reflections in mirrors. Refer to DG / WINDOWS VISUAL PRIVACYVisual privacy is required from other spaces. |