Technical Data
Acoustics
N/A
|
Ceiling
N/A
|
Communications
N/A
|
Cooling
N/A
|
Doors
DT
DOOR TYPEStandard door Refer to DG / DOORS |
Drainage
SD
SANITARY DRAINAGE FIXTURES2 drainage outlets Refer to DG / DRAINAGE |
Fire Protection
PFE
PORTABLE FIRE EXTINGUISHER/ BLANKETPortable fire extinguisher/fire blanket - to comply with NCC. |
Floor
FF
FLOOR FINISHSteel troweled concrete Refer to DG / FLOOR FLOOR WASTEFloor waste(s) are to be included with falls in floor. Refer to DG / DRAINAGE (& TRADE WASTE) FLOOR - OTHERMinimum threshold at door to enable equipment access. Falls to outside. Refer to DG / FLOOR |
Gas
N/A
|
Heating
N/A
|
Illumination
LUX
LUX LEVEL160 lux Refer to DG / LIGHTING LIGHTING CONTROLLighting control requirements as outlined in Design Guide. Refer to DG / LIGHTING |
Keying
KY
KEYING GENERALKeyed differently (key to differ) Refer to SG455 / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Maintenance & Cleaning Refer to SG455 / DOOR HARDWARE / KEYING |
Light
N/A
|
Power
GPO
GENERAL POWER OUTLETS1 double socket outlet Refer to DG / POWER |
|
Security
C
SECURITY LEVEL CCategory C - Medium Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGEDoor signage required. Suggested text "Store" Refer to DG / SIGNS |
Ventilation
OTH
EXHAUST - OTHERRefer to Design Guide for specific ventilation requirements. Refer to DG / VENTILATION |
Wall
OTH
WALL - OTHERSplashback 450mm high to basin/sink Refer to SG / LINING IMPACT RESISTANCEImpact resistant walls are recommended. Refer to DG / FABRIC |
Water
CW
COLD WATERRequired to 1 x basin, 1 x hose cock. Refer to DG / WATER |
Windows
N
WINDOWS - NWindows are not required for this space. VISUAL PRIVACYVisual privacy is required from other spaces. |