Technical Data
Acoustics
R2R
ROOM TO ROOM NOISENoise to and from adjacent rooms should be considered. |
Ceiling
RES
RESISTANCEWater resistant and non-absorbative ceiling required Refer to DG / CEILING CEILING - OTHERAll joints to be sealed for hygiene Refer to DG / CEILING |
Communications
CO
COMMUNICATIONS/TELEPHONE POINTSCommunications/Telephone point requirements and considerations apply. Refer to DG / COMMUNICATIONS AUDIO VISUAL REQUIREMENTSAudio visual requirements and considerations apply. Refer to DG / COMMUNICATIONS |
Cooling
N/A
|
Doors
DT
DOOR TYPEConnection to Servery/Preparation Refer to DG / DOORS |
Drainage
N/A
|
Fire Protection
FD
FIRE DETECTION/ALARMSFire detection/alarms to comply with NCC. PORTABLE FIRE EXTINGUISHER/ BLANKETPortable fire extinguisher/fire blanket - to comply with NCC. FIRE HOSE REELFire Hose Reels as required to comply with NCC. Refer to DG / BUILDING REGULATIONS & BUILDING CODE OF AUSTRALIA / SERVICES AND EQUIPMENT |
Floor
FF
FLOOR FINISHIndustrial sheet flooring Refer to DG / FLOOR FLOOR - OTHERCoved skirtings and solid plinths under benches Refer to DG / FLOOR |
Gas
N/A
|
Heating
H
HEATINGProvide heating where regionally appropriate. Refer to DG / HEATING |
Illumination
N/A
|
Keying
KY
KEYING GENERALKeyed alike - Canteen Refer to SG455 / DOOR HARDWARE / KEYING |
Light
DL
DAYLIGHTDaylight is recommended for this space. |
Planning
m^2
AREAType 1 - 7 m2 for Core seven Type 2 - 9 m2 for Core fourteen Type 3 - 11 m2 for Core twenty one Refer to DG / AREA PLANNING - OTHERVermin proof and non-vermin harbouring If directly accessible from Communal Space (PS503.01) refer to Design Guide – Entertainment Venue (place of public entertainment) Refer to DG / AREA PROPORTIONTo suit furniture layout Must comply with food regulation requirements Refer to DG / AREA |
Power
N/A
|
Security
D
SECURITY LEVEL DCategory D - Moderately High Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGEDoor signage required. Suggested text " Office/Store" Refer to DG / SIGNS SIGNS GENERAL2 Prohibition signs "No Smoking" symbol, in conspicuous positions on opposite walls. Refer to DG / SIGNS |
Ventilation
N/A
|
Wall
OTH
WALL - OTHERWater & impact resistant walls required, (prefereably rendered & painted walls for hygiene and easy cleaning). Must not harbour vermin Refer to SG / LINING |
Water
N/A
|
Windows
Y
WINDOWS - YWindows are required for this space. |