Technical Data
Acoustics
R2R
ROOM TO ROOM NOISENoise to and from adjacent rooms should be considered. |
Ceiling
RES
RESISTANCEWater resistant ceiling required. Refer to DG / CEILING |
Communications
N/A
|
Cooling
N/A
|
Doors
DT
DOOR TYPEDoor for visual privacy. Refer to DG / DOORS |
Drainage
SD
SANITARY DRAINAGE FIXTURES3 drainage outlets. Refer to DG / DRAINAGE |
Fire Protection
N/A
|
Floor
FF
FLOOR FINISHCeramic tiled floor finish. Refer to DG / FLOOR FLOOR WASTEFloor waste(s) are to be included with falls in floor. Refer to DG / DRAINAGE (& TRADE WASTE) FLOOR - OTHERWaterproofed floor with coved skirting; floor waste with falls in floor. Refer to DG / FLOOR |
Gas
N/A
|
Heating
N/A
|
Illumination
LUX
LUX LEVEL160 lux. Refer to DG / LIGHTING LIGHTING CONTROLLighting control requirements as outlined in Design Guide. Refer to DG / LIGHTING |
Keying
KY
KEYING GENERALKeyed alike - Toilets. Refer to SG / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration & Staff. Refer to SG / DOOR HARDWARE / KEYING |
Light
N/A
|
Power
GPO
GENERAL POWER OUTLETSGeneral power outlets required. Refer to DG / POWER |
|
Security
A
SECURITY LEVEL ACategory A - Low Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGETOILET Braille & Tactile Door Sign or "AMBULANT TOILET" Braille & Tactile Door Sign to each cubicle. Refer to DG / DOOR SIGNS |
Ventilation
EXH
GENERAL EXHAUSTMechanical Exhaust of toilet areas may be required. Refer to DG / VENTILATION |
Wall
OTH
WALL - OTHERWater resistant splashback 450mm high to basin. Water and impact resistant walls are required. Coved skirting also recommended. Refer to SG / LINING IMPACT RESISTANCEImpact resistant walls are recommended. Refer to DG / FABRIC |
Water
|
Windows
Y
WINDOWS - YWindows are required for this space. |