Technical Data
Acoustics
NL
NOISE LEVELSNoise levels within this space should be considered. Refer to DG / ACOUSTICS / INTERNAL NOISE LEVELS ROOM TO ROOM NOISENoise to and from adjacent rooms should be considered. |
Ceiling
ACC
ACOUSTIC CEILING TYPEStandard ceiling. Refer to DG / CEILING |
Communications
OTH
COMMUNICATIONS - OTHERInclude Alarm Call System. Refer to DG / COMMUNICATIONS COMMUNICATIONS/TELEPHONE POINTSCommunications/Telephone point requirements and considerations apply. Refer to DG / COMMUNICATIONS WIRELESS ACCESS POINTS |
Doors
DT
DOOR TYPEDoor for privacy within the clinic, separated from waiting. A moveable privacy screen or system should be included within the space. Refer to DG / DOORS |
Drainage
SD
SANITARY DRAINAGE FIXTURES4 drainage outlets. Refer to DG / DRAINAGE |
|
Fire Protection
FHR
FIRE HOSE REELFire Hose Reels as required to comply with NCC. Refer to DG / BUILDING REGULATIONS & BUILDING CODE OF AUSTRALIA / SERVICES AND EQUIPMENT |
Floor
FF
FLOOR FINISHCarpet floor finish with industrial sheet flooring at sink and ceramic tiles in toilets. Refer to DG / FLOOR FLOOR WASTEFloor waste(s) are to be included with falls in floor. Refer to DG / DRAINAGE (& TRADE WASTE) |
|
Heating
H
HEATINGProvide heating where regionally appropriate. Refer to DG / HEATING |
Illumination
LUX
LUX LEVEL240 lux. Refer to DG / LIGHTING LIGHTING CONTROLLighting control requirements as outlined in Design Guide. Refer to DG / LIGHTING |
Keying
KY
KEYING GENERALKeyed alike - Clinic. Refer to SG / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration & Staff. Refer to SG / DOOR HARDWARE / KEYING |
Light
N/A
|
Power
CM
CABLE MANAGEMENTCable management to be considered. Refer to DG / POWER GENERAL POWER OUTLETS3 double socket outlets. Refer to DG / POWER |
|
Security
B
SECURITY LEVEL BCategory B - Moderately Low Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGEDoor signage required. Suggested text "Community Clinic". Refer to DG / DOOR SIGNS |
Ventilation
NV
NATURAL VENTILATIONProvide Natural Ventilation. Refer to DG / VENTILATION and DG / AIR MOVEMENT / NATURAL VENTILATION |
Wall
OTH
WALL - OTHERSplashback 450mm high to basin, sink & bench. Refer to SG / LINING |
Water
HW
TEMPERED WATERRequired to 1 x sink & basin. Refer to DG / WATER COLD WATERRequired to 1 x sink, basin & WC. Refer to DG / WATER |
Windows
Y
WINDOWS - YWindows are required for this space. |