Technical Data
Acoustics
N/A
|
Ceiling
ACC
ACOUSTIC CEILING TYPEStandard ceiling. Refer to DG / CEILING |
Communications
AV
AUDIO VISUAL REQUIREMENTSAudio visual requirements and considerations apply. Refer to DG / COMMUNICATIONS WIRELESS ACCESS POINTS |
Cooling
N/A
|
Doors
DT
DOOR TYPEGlazed double main entry door . Door to internal administration circulation. Refer to DG / DOORS GLAZED DOORSGlazed main entry door. Refer to DG / DOORS |
Drainage
N/A
|
Fire Protection
FHR
FIRE HOSE REELFire Hose Reels as required to comply with NCC. Refer to DG / BUILDING REGULATIONS & BUILDING CODE OF AUSTRALIA / SERVICES AND EQUIPMENT |
Floor
FF
FLOOR FINISHCarpet finish. Refer to DG / FLOOR |
Gas
N/A
|
Heating
H
HEATINGProvide heating where regionally appropriate. Refer to DG / HEATING |
Illumination
LUX
LUX LEVEL320 lux. Refer to DG / LIGHTING LIGHTING CONTROLLighting control requirements as outlined in Design Guide. Refer to DG / LIGHTING |
Keying
MKY
MASTER KEYINGMaster keyed - Administration & Staff. Refer to SG455 / DOOR HARDWARE / KEYING |
Light
DL
DAYLIGHTDaylight is recommended for this space. |
Planning
m^2
AREAType 1 - 6 m2 for Core three Type 2 - 9 m2 for Core seven Type 3 - 13 m2 for Core fourteen Type 4 - 16 m2 for Core twenty one Refer to DG / AREA PLANNING - OTHERAdjacent to clerical office, with reception window/opening and door connection. Refer to DG / AREA PROPORTIONMinimum depths: Type 1 – 2.1 m minimum depth for Core three Type 2– 2.4 m minimum depth for Core seven Type 3 – 2.7 m minimum depth for Core fourteen Type 4 – 2.7 m minimum depth for Core twenty one Refer to DG / AREA |
Power
CM
CABLE MANAGEMENTCable management to be considered. Refer to DG / POWER GENERAL POWER OUTLETSGeneral power outlets required. Refer to DG / POWER |
Security
A
SECURITY LEVEL ACategory A - Low Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGEInformation sign "AUTHORISED STAFF ONLY" on exterior of door to the Administration Circulation. Refer to DG / DOOR SIGNS SIGNS - OTHERInformation sign "ENQUIRIES", near Clerical/Printing Office. Refer to DG / SIGNS |
Ventilation
N/A
|
Wall
PF
PINBOARD FINISHMaximum pinboard finish from floor to 2.1m, for Reception wall and wall with door/hallway leading to internal offices. Refer to SG / LINING |
Water
N/A
|
Windows
Y
WINDOWS - YWindows are required for this space. |