Acoustics
R2R
ROOM TO ROOM NOISENoise to and from adjacent rooms should be considered |
Ceiling
ACC
ACOUSTIC CEILING TYPEStandard ceiling. Refer to DG / CEILING |
Communications
CO
COMMUNICATIONS/TELEPHONE POINTS2 Dual Data points required. Refer to DG / COMMUNICATIONS WIRELESS ACCESS POINTSThis room is to be wireless enabled. Refer to DG / COMMUNICATIONS |
Cooling
MC
MECHANICAL COOLINGMay be required if ventilation is insufficient |
Doors
DT
DOORS TYPENo Window DOORS OTHERSMinimum opening height 2100mm Minimum opening width 1000mm |
Drainage
N/A
|
Fire Protection
PFE
PORTABLE FIRE EXTINGUISHER/BLANKETPortable fire extinguisher to be located adjacent to the door either inside or outside room to comply with NCC. FIRE HOSE REELFire hose reels as required to comply with NCC Refer to DG / BUILDING REGULATIONS & BUILDING CODE OF AUSTRALIA / SERVICES AND EQUIPMENT |
Floor
FF
FLOOR FINISHASV - Anti-static vinyl/Linoleum. Refer to DG / FLOOR |
Gas
N/A
|
Heating
N/A
|
Illumination
OTH
OTHER2 lights minimum, illuminating front and rear of cabinets LUX LEVEL240 lux. Refer to DG / LIGHTING LIGHTING CONTROLManual with motion timer ‐ 30 minutes Refer to DG / LIGHTING |
Keying
KY
KEYING GENERALKeyed Alike ‐ System Administration (SA) Keyed Alike ‐ MainCommunications Room (SA) |
Light
N/A
|
Power
CM
CABLE MANAGEMENTCable management to be considered Refer to DG / POWER POWER - OTHEROther power considerations may apply. Refer to DG / POWER Additional General Power Outlets may be required for Security Equipment. Refer to Security Specifications. Other power considerations may apply Refer to DG / POWER, DG / SPECIAL ELECTRICAL SERVICES |
|
Security
B
Security LevelCategory B- Securable,Lockable Refer to DG/SECURUTY CATEGORY FOR OPENING |
Signs
DSF
DOOR SIGNAGEDoor signage required. Suggested text "Building Communications Room". Refer to DG / DOOR SIGNS SIGNS - OTHERHazard danger sign "ELECTRICAL EQUIPMENT - AUTHORISED PERSONNEL ONLY" on the exterior of door. Refer to DG / SIGNS |
Ventilation
OTH
TEMPERATUREMechanical ventilation mandatory or Mechanical cooling if required. Refer to DG / VENTILATION |
Wall
N/A
|
Water
N/A
|
Room Relationships
This space is found in the Services . This room should be centrally located and secured.This room should be physically located to reduce cable pathway lengths and near building risers.
Maximum fixed cable pathway length is 90M, Use 70M radius as approximate working guide for cable coverage.To be located in a secure location with no external or student access.