Technical Data
Acoustics
N/A
|
Ceiling
OTH
CEILING OTHERWater Resistant and easy clean Ceiling ACOUSTIC CEILING TYPEStandard ceiling Refer to DG / CEILING |
Communications
N/A
|
Cooling
N/A
|
Doors
DT
DOOR TYPEEnsure visual privacy (consider reflections in mirrors). External door to be grill gate. Refer to DG / DOORS |
Drainage
SD
SANITARY DRAINAGE FIXTURES3 Drainage outlets. Refer to DG / DRAINAGE |
Fire Protection
FD
FIRE DETECTION/ALARMSFire detection/alarms to comply with NCC. Refer to DG / THERMAL/SMOKE DETECTORS |
Floor
FF
FLOOR FINISHCT- Ceramic Tiles. Refer to DG / FLOOR FLOOR WASTEFloor waste(s) are to be included with falls in floor. Refer to DG / DRAINAGE (& TRADE WASTE) FLOOR - OTHERCoved skirting tiles at wall Well graded falls to floor waste. |
|
Heating
N/A
|
Illumination
|
Keying
KY
KEYING GENERALKeyed Alike Toilets (T). Refer to SG455 / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration & Staff (AF). Refer to SG455 / DOOR HARDWARE / KEYING |
Light
N/A
|
Planning
m^2
AREA2m2. Refer to DG / AREA PLANNING - OTHERAllow for one WC to be 1.2m wide per Sex per general student toilet group. At least 1 Ambulant cubicle per sex per group of toilets Ensure visual privacy of cubicles. Refer to DG / AREA PROPORTIONSArea varies depending upon number of students. Refer to DG / AREA |
Power
N/A
|
Security
A
SECURITY LEVEL ACategory A - Low Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS |
Signs
DSF
DOOR SIGNAGESIGNS GENERALBraille and Tactile signage as required by access regulations Notice "Assistance required in Access Shower/Toilet when buzzer sounds", in nearest permanently occupied space. Refer to DG / SIGNS |
Ventilation
|
Wall
OTH
WALL - OTHERWater resistant, easy-clean walls. 300mm high Stainless steel splashback to wash trough. Refer to SG / LINING IMPACT RESISTANCEImpact resistant walls are recommended. Refer to DG / FABRIC |
Water
HW
TEMPERED WATERTempered water required to 1 x basin. Refer to DG / WATER COLD WATERCW Required to 1 x basin, 1 x WC (603.02) CW Required to 1 x basin, 1 x urinal (603.03). Refer to DG / WATER |
Windows
OTH
WINDOW - OTHERFixed metal louvres preferred Obscure glazing when required Ensure Visual privacy. Refer to DG / WINDOWS VISUAL PRIVACYVisual privacy is required from other spaces. |