As per current NATSPEC.
As per current NATSPEC except as follows:
Description
Type: Cushion parquet (or wood mosaic)
Grade: Select
Block size:
Block type: Square dressed
Timber species: Spotted Gum or Blackbutt
Termite resistance
Requirement: Timber and plywood must be treated to prevent attack by termites.
As per current NATSPEC except as follows:
GUIDE NOTE: Add the following subclauses to the NATSPEC Building Template / Worksection.
General
One of the following alternative termite resistant timber species or preservative treatments against termite attack is to be used for framing of floors:
Timber floor on slab
GUIDE NOTES:
Sprung timber flooring system
GUIDE NOTE: Insert project specific locations. Refer to the Educational Facilities Standards and Guidelines.
Size (w x d min.): 75 x 35mm
Appendix A. Turn up vapour barrier at the perimeter of the flooring system. Cut and tape to drainage outlets.
Strip flooring
Location
>
Evaporative cooler installations
GUIDE NOTE:In locations where evaporative cooling systems are to be installed or is installed timber flooring is not recommened. The increased humidity levels and the fluctuations of the humidity may have an adverse effect on the timber. Alternative ventilatioin, cooling or flooring materials should be considered.
If timber flooring must be used when an evaporative cooling system is going to be installed or is installed include the following floor schedule.
Requirement: Strip flooring installation in locations where an evaporative cooler is or is to be installed.
Notify the timber-flooring supplier that an evaporative cooling system is or is going to be installed and that there will be an increased humidity level.
The timber must be certified on delivery by the supplier verifying the moisture content of the timber.
Immediately after the timber is delivered it must be strip stacked in its final environment for a minimum of several weeks with the evaporative cooling left on to allow the timber to achieve the desired EMC and stabilise prior to fixing.
Strip flooring installation
Flooring system: To AS 1684.
Stage floor
Edge board to have at least 30% contrast in colour to stage floor colour.
Skirting
Nominal 100 x 32mm thick (finished size) with splay top fixed all perimeter.
GUIDE NOTE: Add the following subclause to the NATSPEC Building Template / Worksection.
Maintenance manual
Size (written instructions): A4 (minimum)
Instructions: Brief precise text with corresponding graphics.
Finish: Laminated.
Location/Distribution:
Requirement
Screw fix 3mm steel sheet to existing floor structure.
As per current NATSPEC.