Technical Data
Acoustics
N/A
|
Ceiling
RES
RESISTANCEWater Resistant Ceiling. Refer to DG / CEILING |
Communications
OTH
COMMUNICATIONS - OTHERInclude Alarm Call System. Refer to DG / COMMUNICATIONS |
Cooling
N/A
|
Doors
DT
DOOR TYPEMinimum width as required by legislation Outward swinging preferred. Solid Core Door without closer preferred. Refer to DG / DOORS |
Drainage
SD
SANITARY DRAINAGE FIXTURES3 drainage outlets. Refer to DG / DRAINAGE |
Fire Protection
N/A
|
Floor
FF
FLOOR FINISHCT - Ceramic Tiles. Refer to DG / FLOOR FLOOR WASTEFloor waste(s) are to be included with falls in floor. Refer to DG / DRAINAGE (& TRADE WASTE) FLOOR - OTHERCoved skirting tiles at wall Falls to floor waste. Tiles are not to have a bevelled edge. Tiling to have flush joints. Avoid abrupt changes in level. Refer to DG / FLOOR |
|
Heating
OTH
HEATING - OTHERInclude local heating to shower area. Refer to DG / HOT WATER HEATERS HEATINGProvide heating where regionally appropriate. Refer to DG / HEATING |
Illumination
|
Keying
KY
KEYING GENERALKeyed Alike Toilets (T). Refer to SG / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration & Staff (AF). Refer to SG / DOOR HARDWARE / KEYING |
Light
N/A
|
Planning
m^2
AREAType 1 - 6m2 Refer to DG / AREA PLANNING OTHERWhere multiple Access WC's provided ensure equal numbers of each hand. Ensure Visual privacy of toilet area. Refer to DG / AREA PROPORTIONSDesigned to meet regulatory requirements. At least 1 Access WC cubicle required per group of toilets. Refer to DG / AREA |
Power
GPO
GENERAL POWER OUTLETS1 double socket outlet. Refer to DG / POWER POWER - OTHEROther power considerations may apply. Refer to DG / POWER |
Security
A
SECURITY LEVEL ACategory A - Low Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS SECURITY - OTHERAlarm Call system with Alarm to Office area. Refer to DG / SPECIAL ELECTRICAL SYSTEMS |
Signs
DSF
DOOR SIGNAGE"TOILET/SHOWER" "TOILET" Refer to DG / DOOR SIGNS SIGNS GENERALBraille and Tactile signage as required by access regulations Notice "Assistance required in Access Shower/Toilet when buzzer sounds", in nearest permanently occupied space. Refer to DG / SIGNS |
Ventilation
EXH
GENERAL EXHAUSTGeneral Exhausted required. Refer to DG / VENTILATION |
Wall
OTH
WALL - OTHERBrickwork walls with ceramic tiles to door head height. Refer to SG / LINING IMPACT RESISTANCEImpact resistant walls are recommended. Refer to DG / FABRIC |
Water
HW
TEMPERED WATERRequired to 1 x basin, 1 x shower. Refer to DG / WATER COLD WATERRequired to 1 x basin, 1 x WC, 1 x shower. Refer to DG / WATER |
Windows
OTH
WINDOWS - OTHERIf windows are included obscure glazing and ensure visual privacy when windows open. Refer to DG / WINDOWS VISUAL PRIVACYVisual privacy is required from other spaces. |