Technical Data
Acoustics
R2R
ROOM TO ROOM NOISENoise to and from adjacent rooms should be considered. |
Ceiling
RES
RESISTANCEWater resistant ceiling required. Refer to DG / CEILING |
Communications
OTH
COMMUNICATIONS - OTHERInclude Alarm Call System. Refer to DG / COMMUNICATIONS |
Cooling
N/A
|
Doors
DT
DOOR TYPEImpact resistant door for visual privacy and durability. Refer to DG / DOORS |
Drainage
SD
SANITARY DRAINAGE FIXTURES3 drainage outlets. Refer to DG / DRAINAGE |
Fire Protection
N/A
|
Floor
FF
FLOOR FINISHCeramic tiled floor finish (tile joints be flush). Refer to DG / FLOOR FLOOR WASTEFloor waste(s) are to be included with falls in floor. Refer to DG / DRAINAGE (& TRADE WASTE) FLOOR - OTHERWaterproofed floor with coved skirting; floor waste with falls in floor. Refer to DG / FLOOR |
Gas
N/A
|
Heating
OTH
HEATING - OTHERInclude local heating to shower area. Heating lamps may be included to provide local heating to shower area. Refer to DG / HOT WATER HEATERS HEATINGProvide heating where regionally appropriate. Refer to DG / HEATING |
Illumination
LUX
LUX LEVEL160 lux. Refer to DG / LIGHTING LIGHTING CONTROLLighting control requirements as outlined in Design Guide. Refer to DG / LIGHTING |
Keying
KY
KEYING GENERALKeyed alike - Toilets. Refer to SG / DOOR HARDWARE / KEYING MASTER KEYINGMaster keyed - Administration & Staff. Refer to SG / DOOR HARDWARE / KEYING |
Light
N/A
|
Power
GPO
GENERAL POWER OUTLETSGeneral power outlets required. Refer to DG / POWER |
|
Security
A
SECURITY LEVEL ACategory A - Low Security Level applies. Refer to DG / SECURITY CATEGORIES FOR OPENINGS SECURITY - OTHERAlarm Call system with Alarm to Office area. Refer to DG / SPECIAL ELECTRICAL SYSTEMS |
Signs
DSF
DOOR SIGNAGEACCESSIBLE UNISEX TOILET Braille & Tactile Door Sign. Refer to DG / DOOR SIGNS SIGNS GENERALNotice "Assistance required in Access Shower/Toilet when buzzer sounds", in nearest permanently occupied space. Refer to DG / SIGNS |
Ventilation
EXH
GENERAL EXHAUSTToilet Exhaust required. Refer to DG / VENTILATION |
Wall
OTH
WALL - OTHERWater and impact resistant to 2100mm high; brickwork is preferable for easy cleaning. Coved skirting also recommended. Refer to SG / LINING IMPACT RESISTANCEImpact resistant walls are recommended. Refer to DG / FABRIC |
Water
HW
TEMPERED WATERRequired to 1 x basin & shower. Refer to DG / WATER COLD WATERRequired to 1 x basin, WC & shower. Refer to DG / WATER |
Windows
Y
WINDOWS - YWindows are required for this space. |